Technical Specifications:

  • Siemens LGK16.622 A17 110V controls gas, oil or duel fuel forced draft bruners.
  • Semi-automatic Startup
  • Supply Voltage: 110V
  • Prepurge time with air damper open: 65s
  • Pre-ignition time: 4s
  • Interval from start-up to the beginning of the air pressure check: 8s
  • Post purge time: 12s
  • Ignition safety time: 2s
  • Permissible afterburn time: 12s

Siemens LGK16.622 A17 Datasheet

Siemens LGK16.622 110v Datasheet / Manual

Siemens LGK16.622 110V Dimensions

Siemens LKG16.622 Control Box Dimensions

Are you looking for the 240V version of this product? If so please click the link below: